CDCS study material has a high quality service team. First of all, the authors of study materials are experts in the field. They have been engaged in research on the development of the industry for many years, and have a keen sense of smell for changes in the examination direction. Experts hired by CDCS exam questions not only conducted in-depth research on the prediction of test questions, but also made great breakthroughs in learning methods. With CDCS training materials, you can easily memorize all important points of knowledge without rigid endorsements. With CDCS Exam Torrent, you no longer need to spend money to hire a dedicated tutor to explain it to you, even if you are a rookie of the industry, you can understand everything in the materials without any obstacles. With CDCS exam questions, your teacher is no longer one person, but a large team of experts who can help you solve all the problems you have encountered in the learning process.

EXIN CDCS Exam Syllabus Topics:

TopicDetails
Topic 1
  • Data Centre Life Cycle and Standards: This section of the exam measures the skills of data center professionals and covers the various stages involved in the life cycle of a data center, from planning and design to implementation and decommissioning.
Topic 2
  • Designing and Implementing a Data Centre: In this module, the exam assesses the knowledge of Exin data center professionals tasked with the design and implementation of data centers. Candidates will learn the key principles of creating an efficient data center layout, including considerations for scalability, redundancy, and security.
Topic 3
  • Data Centre Environmental Considerations and Efficiency: This section evaluates the proficiency of data center professionals in addressing environmental factors and promoting efficiency within data center operations. The target audience, including data center managers and engineers, will be tested on their ability to identify and implement measures that enhance energy efficiency, cooling management, and sustainable practices.

>> CDCS Reliable Test Review <<

Exam CDCS Simulations | Test CDCS Preparation

The passing rate of our products is the highest. Many candidates can also certify for our EXIN CDCS study materials. As long as you are willing to trust our EXIN CDCS Preparation materials, you are bound to get the EXIN CDCS certificate. Life needs new challenge. Try to do some meaningful things.

EXIN EPI Certified Data Centre Specialist Sample Questions (Q15-Q20):

NEW QUESTION # 15
It is assumed that EMF shielding material must be installed as the EMF levels coming from the transformer room into the computer room are measured at 100mG. The transformer room is approximately 10 meters away from the computer room and is separated by a corridor. You can assume that no physical issues are present for installing shielding material at any area/location.
Where should you recommend the shielding material to be installed?

  • A. As close as possible to the transformer room
  • B. Shielding is not required to be installed as 100mG is within the acceptable levels for computer rooms
  • C. As close as possible to the computer room
  • D. It does not matter, either close to the transformer room or the computer room is okay as there is no impact to cost or shielding material performance

Answer: A

Explanation:
EMF shielding is most effective when installed close to the source of the EMF, which in this case is the transformer room. Shielding at the source contains the magnetic fields before they spread, minimizing exposure throughout the facility, including the computer room.
Detailed Explanation:
Placing shielding close to the EMF source minimizes the area impacted by electromagnetic interference, as it reduces the distance over which the EMF can spread. Shielding materials near the source can absorb or redirect EMF, providing the most effective reduction of EMF levels in adjacent spaces, like the data center.
EPI Data Center Specialist References:
EPI data center training advises positioning shielding close to the EMF source to contain fields more effectively and reduce interference in critical areas. This method is more efficient and cost-effective, as it limits the spread of EMF from the point of origin.


NEW QUESTION # 16
Management has requested a 15-minute battery bank assuming full load on the UPS. The UPS vendor has provided the following specifications of the UPS:
* Rated power: 30 kVA
* Rectifier input voltage: 400 V/3 phase
* Rectifier input power factor: 0.8
* Battery rated voltage: 384 V
* Number of cells: 192
* End of discharge voltage: 308 V
* Inverter output voltage: 400 V/3 phase
* Inverter output power factor: 0.8
What information is missing to perform the battery calculation?

  • A. Load imbalance on the phases
  • B. Inverter efficiency
  • C. Available battery charging current
  • D. UPS efficiency

Answer: D

Explanation:
To determine the required capacity of the battery bank for the 15-minute runtime at full load, one must know the total power requirement that the battery bank must supply. The specifications provided include most of the necessary details, such as rated power, input voltage, battery voltage, and discharge voltage. However, one critical piece of information is missing: the UPS efficiency.
Detailed Explanation:
In a data center UPS system, the battery bank is designed to supply power for a set duration when there is an input power failure. The UPS efficiency affects the actual power the UPS can deliver to the load compared to the power it draws from the batteries. The efficiency factor is necessary to accurately calculate the required capacity of the battery bank since it determines how much input power is needed from the batteries to supply the load at full capacity. The formula typically used to determine battery capacity involves factoring in UPS efficiency, as it allows you to understand the losses within the UPS system.
If UPS efficiency is not considered, there would be an inaccurate estimation of the actual power needed from the batteries. For instance, if a UPS has 90% efficiency, only 90% of the power drawn from the batteries reaches the load. Without knowing this efficiency, it is not possible to calculate the battery bank size accurately, as you cannot accurately estimate the losses within the UPS itself.
EPI Data Center Specialist References:
According to EPI Data Center Specialist training, understanding the UPS efficiency is essential for battery sizing. Without it, the calculations could lead to either undersizing or oversizing the battery bank, which affects both reliability and cost-effectiveness of the UPS system. The EPI Data Center Specialist course emphasizes that battery sizing must account for all losses within the UPS system, with efficiency being a primary factor in these calculations.


NEW QUESTION # 17
A computer room with a raised floor has been designed with racks in a hot/cold aisle setup.
What should you recommend for the placement of down-flow air conditioners?

  • A. Air conditioners should always be placed at both sides of each row of racks
  • B. Air conditioner placement has no influence on cooling effectiveness and efficiency. Hence, they can be placed at any convenient location.
  • C. Air conditioners perpendicular to (at the end of the row of) the Hot-Aisle
  • D. Air conditioners perpendicular to (at the end of the row of) the Cold-Aisle

Answer: D

Explanation:
In a hot/cold aisle configuration, placing down-flow air conditioners perpendicular to the cold aisle ensures that cool air is directed efficiently into the cold aisles where server intakes are located. This layout allows for optimal cooling performance by aligning the airflow directly with the equipment intakes, minimizing hot spots and enhancing cooling efficiency.
Detailed Explanation:
With a raised floor design, cold air from the air conditioners is supplied into the cold aisle, where server intakes are located. Positioning the air conditioning units perpendicular to the cold aisles ensures that cool air is delivered directly into these aisles, preventing air mixing and optimizing cooling. This setup takes full advantage of the airflow management strategy inherent to the hot/cold aisle configuration.
EPI Data Center Specialist References:
EPI guidelines on cooling emphasize that down-flow air conditioners should be positioned to maximize the effectiveness of cold aisle delivery, which improves cooling efficiency and helps maintain consistent temperatures across server racks.


NEW QUESTION # 18
When installing a raised floor, can we use a spirit level bar to level the floor?

  • A. Yes, spirit level bars can be used as long as their length is longer than 60 cm/2 ft (the size of a typical raised floor tile).
  • B. Yes, but spirit level bars can only be used in the vertical plane.
  • C. No, because using a spirit level bar, a measurement error will be transferred from pedestal to pedestal.
  • D. Yes, using a spirit level bar for raised floors higher than 40 cm is preferred.

Answer: C

Explanation:
A spirit level bar should not be used for leveling a raised floor, as measurement errors are likely to propagate from one pedestal to the next. Spirit levels can introduce cumulative errors, leading to uneven floors, particularly in large installations where precise leveling is critical.
Detailed Explanation:
Using a laser level or a precision leveling device is recommended to ensure accuracy across all floor tiles. Spirit levels, while adequate for short spans, can transfer small inaccuracies from one pedestal to another, which can cause alignment issues and floor instability over time.
EPI Data Center Specialist References:
EPI data center guidelines discourage the use of spirit levels for raised floors. Instead, they advocate for precision tools like laser levels that ensure consistency and accuracy in large-scale installations, aligning with best practices for raised floor construction.


NEW QUESTION # 19
The computer room has high levels of H2S gas contamination. What is the best option to resolve this issue?

  • A. Provide more air changes per hour by adding more fresh air to the computer room.
  • B. Vacuum the whole room using a HEPA/S-Class-based filter.
  • C. Install air-scrubbers.
  • D. Clean the room and racks with a damp/wet cloth.

Answer: C

Explanation:
High levels of H2S (hydrogen sulfide) gas contamination in a computer room are best addressed by installing air-scrubbers. Air-scrubbers can effectively filter out contaminants, including corrosive gases like H2S, ensuring clean air circulation and protecting sensitive IT equipment from potential corrosion and damage.
Detailed Explanation:
Air-scrubbers are designed to remove various airborne contaminants and are particularly useful in environments where corrosive gases are present. These systems use filters or chemical reactions to neutralize harmful substances, making them ideal for data centers that need to maintain high air quality for equipment reliability.
EPI Data Center Specialist References:
EPI guidelines suggest air-scrubbing technologies to remove contaminants that pose risks to electronic equipment, maintaining air quality and reducing corrosion risk.


NEW QUESTION # 20
......

The CDCS software supports the MS operating system and can simulate the real test environment. In addition, the CDCS software has a variety of self-learning and self-assessment functions to test learning outcome, which will help you increase confidence to pass exam. The contents of the three versions are the same. Each of them neither limits the number of devices used or the number of users at the same time. You can choose according to your needs. CDCS Study Materials provide 365 days of free updates, you do not have to worry about what you missed.